Asbestos Management Survey Report
Taihape Hospital, Main Maternity Building
Exterior Asbestos Assessment.
Repo
r
t P
r oduc
tio
n
Survey Conducted by:
Haretini Wakefield
Date of Survey:
16th of March 2018
Position in Company:
Operations Project Manager
Assessor Number:
AA18020017
Expiry Date:
9 February 2023
Signature:
H. Wakefield
Survey Prepared by:
Ali Lind
Date Survey Prepared:
26th of March 2018
Position in Company:
Operations Project Manager
Assessor Number:
AA17090140
Expiry Date:
5 September 2022
Signature:
Survey Reviewed by:
Bruce Wakefield
Date of Review:
02nd of April 2018
Position in Company:
Managing Director
Assessor Number:
AA16090111
Expiry Date:
5 September 2021
Signature:
B. Wakefield
3
Contents Page
Section 1
•
Report Details
•
Introduction
•
Survey Methodology
•
General Recommendations for Asbestos Cement Products
•
General Recommendation for Asbestos Insulation, Coatings
or Insulating Board (AIB)
•
Survey Summary & Recommendations
•
Risk Assessment Methods
Section 2
•
Identification & Photographic Register Sheets
•
Survey Recommendations
•
Survey Record Sheets
•
Laboratory Certificate of Analysis
•
Management Inspection Record
4
Introduction
Further to an invitation from Mr. Grant Hood
(WDHB – Whanganui District Health Board.)
AISL - Asbestos Inspection Services Limited was requested to carry out a
Management Survey at -
Taihape Hospital, Maternity Block, Exterior Location.
There are 2 designated categories of Asbestos surveys currently available.
These are listed below:
Management Survey
Standard sampling, identification and assessment survey (Sampling Survey),
the purpose of which is to locate as far as reasonably Practicable the presence
and extent of any suspect asbestos containing materials in the building and
their condition. This is done by the collection and analysis of samples of
suspect asbestos containing materials.
Refurbishment / Demolition Survey
Full access sampling and identification survey (Pre-demolition/Major
Refurbishment Survey). This type of survey is used to locate and describe as far
as reasonably practicable, all asbestos containing materials in the building and
may involve destructive inspection as necessary to gain access to all areas,
including those that may be difficult to reach. A full sampling programme is
undertaken to identify possible asbestos containing materials and estimates of
the volume and surface areas of asbestos containing materials made.
Access arrangements were made with aid of Mr. Grant Hood (Whanganui District
Health Board) to ensure all accessible areas were surveyed during the project.
The survey was carried out on 16/03/2018 and completed 10 days thereafter.
The survey was to include for visual inspection within the above premises.
The survey was undertaken and completed by members of the AISL – Asbestos
Inspection Services Limited survey team.
During the survey the building remained un-occupied.
5
Disclaimer
Every effort has been made to identify all asbestos materials so far as was
reasonably practicable to do so within the scope of the survey and
the attached report. Methods used to carry out the survey were agreed with the
client prior to any works being commenced.
Survey techniques used involves trained and experienced surveyors using the
combined approach about visual examination. and bulk sample collections
where required.
It is always possible after a survey that asbestos based materials may remain
in the property or area covered by that survey, this could be due to several
reasons:
•
Asbestos materials existing outside the scope of the survey.
•
Materials may be concealed or hidden by other items or covered surfaces
i.e. paint, over boarding, concealing etc. Where this is the case then
its discovery will be limited.
•
Asbestos may well be hidden as part of the structure to a building and
not visible until the structure is demolished later.
•
Fragments from previous asbestos removal projects may well be
present in various areas; general asbestos fragments do not form
part of this survey however all good intentions are made for its
discovery.
Where an area has been formerly stripped of asbestos i.e. plant rooms,
ducts etc. and new coverings added, it must be pointed out that
asbestos removal techniques have improved steadily over the years since its
initial introduction. Most particularly would be the Health and Safety at Work
(Asbestos) Regulations 2016, that outline enforceable strategies. Asbestos
removal prior to this regulation would not be of today’s standard and
therefore fragments may be present beneath new coverings.
This survey will detail areas accessed and all samples taken, where an area is not
covered by this survey it will be due to No Access for one reason or other i.e.
working technicians, delicate location or just simply no admittance. It may have
been necessary for the restrictions of the surveyor’s specialist to
be confirmed prior to the survey.
Admittance for the survey may be restricted for many reasons outside our
control such as height, deadlines to others, steady complications
or confined space. Where electrical equipment is present and presumed in the
way of the survey no access will be attempted until proof of its safe state is
given. Our operatives have a duty of care under the Health and Safety at Work
Act (2016) for both themselves and others.
6
Disclaimer
In the structure where asbestos has been located and not all zones have been
examined, any material that is found to be suspicious and not detailed as part of
the survey should be treated with caution and sampled accordingly.
Certain materials contain asbestos to variable grades and some may be
less densely contaminated at certain locations (Artex for example). Where this is
the case the sample taken may not be representative of the whole
product throughout, therefore composite sampling is therefore encouraged.
Where a survey is carried out under the guidance of the owner of the property or
his representative, then the survey will be as per his/her instructions and
supervision at that time.
Asbestos Inspection Services Limited cannot accept any liability for loss,
injury, damage or penalty issues due to errors or oversights contained within
this report.
Asbestos Inspection Services Limited cannot be held responsible for any
damage caused as part of this survey carried out on your behalf. Due to the
landscape and stipulation of sampling for asbestos some danger is inevitable
and will be limited to just that necessary for the taking of the sample.
7
General Recommendations for Asbestos Cement Products.
Work with cement products containing asbestos is covered by the Management and
Removal of Asbestos (November 2016) Approved Code of Practice.
An assessment of all proposed works which may disturb any asbestos should be
carried out to launch the risk existing, the appropriate precautions must be adopted
to control any exposure. This should combine the succeeding over-all principles:
•
Where work on asbestos cement is inevitable, keep the materials wet
during work and avoid breakage wherever possible. Acceptable PPE
must be worn always.
•
Avoid using power tools. If deemed necessary to use power tools set at the
lowest possible speed, exhaust ventilation such as cowls must be fitted to
power tool and utilising the “investigation technique” with high efficiency H
type vacuum units.
•
Organise the work in a single controlled location where practicable, to
streamline control and supervision. Isolate working areas using warning
signs and tape barriers, or in case of significant fibre levels by means of a
sealed polythene work enclosure and negative pressure equipment. Air
tests must also be carried out by an independent asbestos assessor.
•
Signify respirator zones where the Control Limit is likely to be exceeded
and ensure that all persons entering the zones wear appropriate RPE/PPE
are trained in its use.
•
Ensure that those persons employed in working on asbestos cement are
suitably trained in the correct working practices, control methods and
anticipation of risks.
•
Keep the work area clean during the work and use methods that abate dust
creation, avoid sweeping and brushing, which will make dust airborne.
•
Dispose of asbestos cement waste safely as Asbestos Waste under the
statutory consignment note procedures in accordance with the Health
and Safety at Work (Asbestos) Regulations 2016.
•
Avoid further disturbance of asbestos cement products wherever possible
by relocating or re-routing facilities.
•
Clearly identify and label any asbestos cement products.
8
General Recommendations for Asbestos Insulation,
Coatings or Insulating Board (AIB)
Where the materials are in safe condition and the risk of disturbance is small, they
can be maintained on site. They should be identified with adequate warning signs
and routinely inspected for damages. All asbestos materials should not be drilled,
abraded or disturbed in any way.
All asbestos containing materials should be removed prior to any planned
refurbishment or demolition works, where damage is likely to be sustained during
the occupant’s activities or where future decline is likely.
Work on any of these items may only be carried out by a specialist contractor
licensed under the Health & Safety at Work Act 2016. The selected contractor is
required to notify the WSNZ at least 5 days prior to commencement of the works,
and to provide a written Method Statement as follows:
•
Full explanation of the works to be carried out and its duration.
•
Type, quantity and location of asbestos to be removed.
•
Anticipated exposure levels and persons affected.
•
Enclosure construction details, layout and location, signage and
ventilation.
•
Protections to be adopted to minimize exposure to lowest possible level
and to control release of asbestos fibre beyond the work area.
•
Validation for any withdrawal from preferred methods, e.g. where wet
stripping cannot be used.
•
Type, use and decontamination of RPE/PPE
•
Waste removal and disposal procedures
•
Training and instruction of employees
•
Emergency procedures on site
9
total risk score of between 0 and 12 is calculated using four categories
that are evaluated by the surveyor against given values. The criteria
and the respective values are as follows:
Product Type
1
Asbestos reinforced composites such as plastics, resins, mastic,
roofing felt, vinyl tiles, paints and decorative finishes, asbestos
cement products.
2
Asbestos insulation board, mill boards, other low-density insulation
boards, asbestos textiles, gaskets, ropes and woven textiles,
asbestos paper and felt.
3
Thermal insulation (e.g. pipe and boiler lagging), sprayed asbestos,
loose asbestos, asbestos mattresses and packing.
Condition/Extent of Damage
0
Good condition, no visible damage.
1
Low damage, a few scratches or surface marks, broken edges on
boards, tiles etc.
2
Medium damage, significant breakage of materials or several small
areas where material has been damaged, revealing loose asbestos
fibres.
3
High damage or delamination of materials, sprays and thermal
insulation. Visible asbestos debris.
Surface Treatment
0
Composite materials containing asbestos, such as reinforced
plastics, resins, vinyl tiles.
1
Enclosed sprays and lagging, asbestos insulation board with exposed
surface painted or encapsulated, asbestos cement products.
2
Unsealed asbestos insulation board or encapsulated lagging and
sprays.
3
Unsealed lagging and sprays.
10
Material Assessment Methods
11
Material Assessment Methods
Asbestos Type
1
Chrysotile (white) asbestos.
2
Amosite (brown) asbestos.
3
Crocidolite (blue) asbestos.
The algorithms shown against each situation are added together to give a total material
risk score, for conciseness, the register we have prepared contains only the total risk
score rather than the component scores.
The total score for each situation can be broadly classified using the following bands:
Material Risk Score
0 - 3 Very Low Risk
4 - 6 Low Risk
7 – 9 Medium Risk
10 – 12 High Risk
It is likely that high risk items will be highlighted in the report text and that some
immediate action will be required.
Other items may also be measured for consideration where the decision of the
surveyor recommends this would be beneficial.
12
Priority Assessment Formula
A priority risk score of between 0 and 12 is calculated using four categories that
are evaluated by the duty holder.
Although a surveyor may have some of the information which will contribute to
the risk assessment and may be part of an assessment team, the duty holder is
required to make a risk assessment based on the survey findings and their
detailed knowledge of the activities carried out within the premises. The criteria
and the respective values are as follows:
Normal occupant activity
Assessment
Score
Examples of score variables
factor
Main type of
0
Rare disturbance activity (e.g. little used store room)
activity in area
1
Low disturbance activities (e.g. office type activity)
2
Periodic disturbance (e.g. industrial or vehicular
activity which may contact ACMs)
3
High levels of disturbance, (e.g. fire door with
asbestos insulating board)
Secondary
activities for
As above
area
13
Priority Assessment Formula
Likelihood of disturbance
Assessment
Score
Examples of score variables
factor
Location
0 Outdoors
1 Large rooms or well-ventilated areas
2 Rooms up to 100 m2
3 Confined spaces
Accessibility
0 Usually inaccessible or unlikely to be disturbed
1 Occasionally likely to be disturbed
2 Easily disturbed
3 Routinely disturbed
Extent/amount
0 Small amounts or items (e.g. strings, gaskets)
1 <10 m2 or <10 m
2 10 m2 to 50 m2 or 10 m to 50 m
3 >50 m2 or >50 m
Human exposure potential
Assessment
Score
Examples of score variables
factor
Number of
0
None
occupants
1
1 to 3
2
4 to 10
3
>10
Frequency of
0
Infrequent
use of area
1
Monthly
2
Weekly
3
Daily
Average time
0
<1 hour
area is in use
1
1 to 3 hours
2
3 to 6 hours
3
>6 hours
14
Priority Assessment Formula
Maintenance activity
Assessment
Score
Examples of score variables
factor
Type of
0
Minor disturbance (e.g. possibility of contact
maintenance
when gaining access)
activity
1
Low disturbance (e.g. changing light bulbs in
asbestos insulating board ceiling)
2
Medium disturbance (e.g. lifting one or two
asbestos insulating board ceiling tiles to access
a valve)
3
High levels of disturbance (e.g. removing many
asbestos insulating board ceiling tiles to replace
a valve or for re-cabling)
Frequency of
0
ACM unlikely to be disturbed for maintenance
maintenance
1
<1 per year
activity
2
>1 per year
3
>1 per month
The score for each variable is determined by calculating the average score of the
appropriate factors.
The algorithms shown against each section are added together to give a total priority
risk score, for conciseness, the register we have prepared contains only the overall
risk score rather than the component scores.
Priority Risk Score
0 - 3 Very Low Risk
4 - 6 Low Risk
7 – 9 Medium Risk
10 – 12 High Risk
15
Overal Hazard Risk Assessment Formulae
The material and priority assessment scores provide an overall hazard risk score for
each situation which can be broadly classified using the following table:
Material Assessment
10-12
7-9
5-6
1-4
10-12
t
en
7-9
sm
ses
s
rity A
4-6
rio
P
0-3
Key
High Risk
Total score = 19-24
Medium Risk
Total score = 13-18
Low Risk
Total score = 7-12
Very Low Risk
Total score = 1-6
16
Specific Locations that have been Analysed for asbestos
based material’s or Presumed to Contain Asbestos Containing
material’s.
ID: CARD NO:001
Photograph No.
DSCN0359
Location/Area
Roof-top, membrane. Section 1.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Sample not taken.
Quantity
740.0m2
ID: CARD NO:002
Photograph No.
DSCN0360
Location/Area
Roof-top, electrical room. Roof tiles.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
9.0m2
ID: CARD NO:003
Photograph No.
DSCN0361
Location/Area
Upper window 1. Fascia Board.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
10.7m2
ID: CARD NO:004
Photograph No.
DSCN0362
Location/Area
Upper window 1. Roof membrane.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Sample not taken.
Quantity
35.0m2
ID: CARD NO:005
Photograph No.
DSCN0363
Location/Area
Upper window 1. Soffit Lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
8.12m2
17
ID: CARD NO:006
Photograph No.
DSCN0364
Location/Area
East saw tooth, tiled roof lining.
Sample No.
001.
Laboratory Analysis Findings
Chrysotile (White Asbestos)
Amosite (Brown Asbestos)
Quantity
102.6m2
ID: CARD NO:007
Photograph No.
DSCN0365
Location/Area
East saw tooth, fascia board lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
30.3m2
ID: CARD NO:008
Photograph No.
DSCN0366
Location/Area
Upper window 2. Roof membrane.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Sample not taken.
Quantity
78.0m2
ID: CARD NO:009
Photograph No.
DSCN0367
Location/Area
Upper window 2. Fascia Board.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
47.5m2
ID: CARD NO:010
Photograph No.
DSCN0368
Location/Area
Upper window 2. Soffit Lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
7.15m2
ID: CARD NO:011
Photograph No.
DSCN0369
Location/Area
Roof top garden void, tiled walls.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
13.9m2
18
ID: CARD NO:012
Photograph No.
DSCN0370
Location/Area
Upper window 3. Roof membrane.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Sample not taken.
Quantity
84.0m2
ID: CARD NO:013
Photograph No.
DSCN0371
Location/Area
Upper window 3. Fascia Board.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
30.0m2
ID: CARD NO:014
Photograph No.
DSCN0372
Location/Area
Upper window 3. Soffit Lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
30.0m2
ID: CARD NO:015
Photograph No.
DSCN0373
Location/Area
Roof top section 1, flue pipe.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
.600 diameter pipe, (metal cased).
ID: CARD NO:016
Photograph No.
DSCN0374
Location/Area
East saw tooth, flue 1 pipe.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
.600 diameter pipe, (metal cased).
ID: CARD NO:017
Photograph No.
DSCN0375
Location/Area
East saw tooth, flue 1 pipe.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
.300 diameter pipe, (metal cased).
ID: CARD NO:018
Photograph No.
DSCN0376
Location/Area
Upper window 4. tiled roof lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
8.0m2
19
ID: CARD NO:019
Photograph No.
DSCN0377
Location/Area
Upper window 4. Fascia Board.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
1.5m2
ID: CARD NO:020
Photograph No.
DSCN0378
Location/Area
West saw tooth, tiled roof lining.
Sample No.
002.
Laboratory Analysis Findings
Chrysotile (White Asbestos)
Amosite (Brown Asbestos)
Quantity
102.6m2
ID: CARD NO:021
Photograph No.
DSCN0379
Location/Area
West saw tooth, fascia board lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
16.82m2
ID: CARD NO:022
Photograph No.
DSCN0380
Location/Area
Exterior: tiled wall lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
240.0m2
ID: CARD NO:023
Photograph No.
DSCN0381
Location/Area
Exterior: upper soffit lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
21.85m2
ID: CARD NO:024
Photograph No.
DSCN0382
Location/Area
Exterior: lower soffit lining.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
74.3m2
20
ID: CARD NO:025
Photograph No.
DSCN0383
Location/Area
Eastern: Rear canopy.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
18.96m2
ID: CARD NO:026
Photograph No.
DSCN0384
Location/Area
Exterior: Textured board.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
201.6m2
ID: CARD NO:027
Photograph No.
DSCN0385
Location/Area
Northern elevation. Gable ends.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
18.2m2
ID: CARD NO:028
Photograph No.
DSCN0386
Location/Area
External Entry: Wall panels.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
12.5m2
ID: CARD NO:029
Photograph No.
DSCN0387
Location/Area
Exterior perimeter. Window
compound.
Sample No.
Presumed the presence of ACM.
Laboratory Analysis Findings
Management Survey Only.
Quantity
164 L/ms.
21
22
Inspection Personnel
Taihape Hospital, Maternity Block. Exterior Locations
Date
Name
Company Name
Competency Attained License No Expiry Date
Phone Number Email Address
16th March 2018 Haretini Wakefield Asbestos Inspection Services Limited Licensed Asbestos Assessor
09th of February 2023
+24 22 3234534
[email address]
AA18020017
16th March 2018 Ali
Asbestos Inspection Services Limited Licensed Asbestos Assessor
05th of September 2022 +24 27 8565624
[email address]
Lind
AA17090140
16th March 2018 Bruce Wakefield
Asbestos Inspection Services Limited Licensed Asbestos Assessor AA16090111 05th of September 2021 +64 27 7655123
[email address]
23
Survey Record Sheet
Ref: WDHB
Site Address:
Taihape Hospital, Taihape.
Date: 16/03/2018
Survey Type:
Management Survey
t
n
ity
e
re
re
re
e
t
p
c o
n
re
c tiv
c o
e
tm
y
a
A
c o
a
T
k S
p
s u
f
y p
o
n
k S
re
s
is
c e
c c u
o
c e
n
is
x p
T
to
d
l R
n
l
a
is k S
c t T
itio
o
e
a
l O
a
E
n
ID Card Photo No
s
Sample Ref
Product
Asbestos
d
ity
o
n
tia
ll R
u
e
ri
a
rb
lih
a
n
te
ty R
ra
No
Location/Area Description
n
/Presumed Quantity
Descripti
Type
ri
rfac
b
te
rm
e
tu
m
te
in
o
Action
rod
o
u
s
a
c tiv
is
u
o
a
ri
v e
on
ik
P
C
S
A
M
No
A
L
D
H
P
M
P
O
001 DSCN0359 Roof top membrane
Presumed 740.0m2 Waterproofing Roofing
1 0 0 1 0
0
0
0
0 0
Very low risk Complete a Risk Assessment.
section 1
product
002 DSCN0360 Roof top Electrical
Presumed 9.00m2
Roof tiles
Composite 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
room
Product
003 DSCN0361 Roof top Upper window Presumed 10.70m2 Fascia Board
Compressed 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
1
Board
004 DSCN0362 Roof top Upper window Presumed 35.00m2 Waterproofing Roofing
1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
1 membrane
product
005 DSCN0363 Roof top Upper window Presumed 8.12m2
Soffit lining
Compressed 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
1
board
Board
006 DSCN0364 East saw tooth tiled roof 001
102.60m2 Roof tiles
Composite
1
2 2
1 7
1
0
2
2 7
Medium risk Chrysotile (White Asbestos) Amosite
lining
Product
(Brown Asbestos)
007 DSCN0365 East saw tooth lining
Presumed
30.30m2
Fascia Board
Compressed 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
Board
008 DSCN0366 Roof top Upper window Presumed 78.00m2 Waterproofing Roofing
1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
2 membrane
product
009 DSCN0367 Roof top Upper window Presumed 47.5m2
Fascia Board
Compressed 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
2
Board
010 DSCN0368 Roof top Upper window Presumed 7.15m2
Soffit lining
Compressed 1 0 0 1 0
0
0
0
0 0
Very low risk Complete a Risk Assessment.
2
board
Board
24
Survey Record Sheet
Ref: WDHB
Site Address:
Taihape Hospital, Taihape.
Date: 16/03/2018
Survey Type:
Management Survey
t
n
ity
e
re
re
re
e
t
p
c o
n
re
c tiv
c o
e
tm
y
a
A
c o
a
T
k S
p
s u
f
y p
o
n
k S
re
s
is
c e
c c u
o
c e
n
is
x p
T
to
d
l R
n
l
a
is k S
c t T
itio
o
e
a
l O
a
E
n
ID Card Photo No
s
Sample Ref
Product
Asbestos
d
ity
o
n
tia
ll R
u
e
ri
a
rb
lih
a
n
te
ty R
ra
No
Location/Area Description
n
/Presumed Quantity
Descripti
Type
ri
rfac
b
te
rm
e
tu
m
te
in
o
Action
rod
o
u
s
a
c tiv
is
u
o
a
ri
v e
on
ik
P
C
S
A
M
No
A
L
D
H
P
M
P
O
011 DSCN0369 Roof top Garden
Presumed 13.90m2 Roof tiles
Composite 1 0 0 1 0 0
0
0
0 0 Very low risk Complete a Risk Assessment.
Void
Product
Tiled wall lining
012 DSCN0370 Roof top Upper
Presumed 84.0m2
Waterproofing Roofing
1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
window 3 membrane
product
013 DSCN0371 Roof top Upper
Presumed 30.0m2
Fascia Board
Compressed 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
window 3
Board
014 DSCN0372 Roof top Upper
Presumed 30.0m2
Soffit lining
Compressed 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
window 3
board
Board
015 DSCN0373 Roof top section 1,
Presumed .600mm ᶲ Service pipe
Possible
1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
Metal casing flue
ACM Inner
016 DSCN0374 East saw tooth pipe 1 Presumed .600mm ᶲ Service pipe
Possible
1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
Metal casing flue
ACM Inner
017 DSCN0375 East saw tooth pipe 2 Presumed .300mm ᶲ Service pipe
Possible
1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
Metal casing flue
ACM Inner
018 DSCN0376 Upper window 4,
Presumed 8.00m2
Roof tiles
Composite 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
tiled roof lining
Product
019 DSCN0377 Roof top Upper
Presumed 1.5m2
Fascia Board
Compressed 1 0 0 1 0
0
0
0
0 0 Very low risk Complete a Risk Assessment.
window 4
Board
020 DSCN0378 West saw tooth tiled 002
102.60m2 Roof tiles
Composite
1 2
2
1 7
1
0
2
2 7
Medium risk Chrysotile (White Asbestos) Amosite
roof lining
Product
(Brown Asbestos)
25
Survey Record Sheet
Ref: WDHB
Site Address:
Taihape Hospital, Taihape.
Date: 16/03/2018
Survey Type:
Management Survey
t
n
ity
e
re
re
re
e
t
p
c o
n
re
c tiv
c o
e
tm
y
a
A
c o
a
T
k S
p
s u
f
y p
o
n
k S
re
s
is
c e
c c u
o
c e
n
is
T
to
d
x p
l R
n
l
a
is k S
c t T
itio
o
e
a
l O
a
E
n
ID Card No Photo No
s
Sample Ref
Product
Asbestos
d
ity
o
n
tia
ll R
u
e
ri
a
rb
lih
a
n
te
ty R
ra
Location/Area
n
/Presumed Quantity
Descripti
Type
ri
rfac
b
te
e
tu
m
te
in
Action
a
rm
c tiv
a
o
v e
Description
rod
o
u
s
is
u
o
ri
on
ik
P
C
S
A
M
No
A
L
D
H
P
M
P
O
021
DSCN0379 West saw tooth
Presumed
16.82m2
Fascia Board
Compressed
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
lining
Board
022
DSCN0380 Exterior: tiled
Presumed 240.0m2 Wall tiles
Composite
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
wall lining
Product
023
DSCN0381 Exterior: Upper Presumed 21.85m2 Soffit lining
Compressed
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
soffit lining
board
Board
024
DSCN0382 Exterior: Lower Presumed 74.30m2 Soffit lining
Compressed
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
soffit lining
board
Board
025
DSCN0383 Rear canopy
Presumed 18.96m2
Canopy lining
Compressed
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
lining
board
Board
026
DSCN0384 Exterior: textured Presumed 201.60m2 Textured lining Compressed
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
lining board
board
Board
027
DSCN0385 Northern elevation, Presumed 18.20m2 Gable lining
Compressed
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
Gable end
board
Board
028
DSCN0386 Entry: Wall panels Presumed 12.50m2 Wall lining board Compressed
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
Board
029
DSCN0387 Exterior perimeter, Presumed 164.0 L/m Putty compound Jointing
1 0 0 1 0
0
0
0
0
0 Very low risk Complete a Risk Assessment.
Window compound
compound
26
Document Outline