This is an HTML version of an attachment to the Official Information request 'Building Code Performance Clause C5.7'.

 
 
 
Act
May 2015 
Information 
Official 
the 
under 
Released 

link to page 3 link to page 3 link to page 4 link to page 4 link to page 5 link to page 5 link to page 5 link to page 6 link to page 7 link to page 7 link to page 7 link to page 8 link to page 9 link to page 9 link to page 10 link to page 10 link to page 12
 
Scope 
This guidance document can be used to ensure that New Zealand Fire Service (NZFS) fire 
appliances can adequately access sites, buildings and structures in the event of an emergency. 
The document specifically details the requirements for fire appliance access, including general 
access to sites or premises, and access around buildings or structures within a site 
(allotment). 
The users of this guideline should be aware that this document is an informative guideline, 
and does not replace any statutory requirements. 
Act
 
Contents 
Context ........................................................................................................................................................................... 3 
Definitions ..................................................................................................................................................................... 3 
NZFS appliances .......................................................................................................................................................... 4 
Types of NZFS fire appliances ...................................................................................................................... 4 
Information 
Appliance type coverage ................................................................................................................................ 5 
Access requirements ................................................................................................................................................. 5 
Carriageway widths ......................................................................................................................................... 5 
Turning areas ..................................................................................................................................................... 6 
Official 
Ensuring clear access ...................................................................................................................................... 7 
Kerb dimensions ............................................................................................................................................... 7 

the 
Building and structure clearance height ................................................................................................. 7 
Gradients (e.g. access ramps) ...................................................................................................................... 8 
Appliance weights (loads) ...................................................................................................................................... 9 
Static loads of appliances............................................................................................................................... 9 
under 
Dynamic loads (on aerial appliances) ..................................................................................................... 10 
Vehicle hardstand requirements .............................................................................................................. 10 

References ................................................................................................................................................................... 12 
 
 
 
 
Released 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 


 
Context 
During an emergency, the NZFS is most efficient and effective when there is suitable provision 
for rapid and unhindered response by its fire appliances.  Poor or inadequate access can result 
in a delayed NZFS response, with the obvious delay to intervention having a direct impact on 
the life safety of occupants and the protection of property.  Due to the nature of the functions 
required to be performed, NZFS fire appliances are generally larger and heavier than those 
used by other emergency services. 
The guidance provided is based around compliance with New Zealand Building Code Clause 
C5, which addresses access and safety for firefighting operations.  More specifically, Clauses 
C5.3 and C5.4 of the Building Code describe the performance requirements relating to fire Act
appliance access: 
“C5.3) Buildings must be provided with access for fire service vehicles to a hard-standing from 
which there is an unobstructed path to the building within 20 m of: 

a)  the firefighter access into the building, and 
b)  the inlets to automatic fire sprinkler systems or fire hydrant systems, where these are 
installed. 
Information 
C5.4) Access for fire service vehicles in accordance with clause C5.3 must be provided to more 
than 1 side of firecells greater than 5,000 m2 in floor area that are not protected by an 
automatic fire sprinkler system. 
Performance requirements in clauses C5.3 to C5.8 do not apply to backcountry huts, detached 
dwellings, within household units in multi-unit dwellings, or to outbuildings, and ancillary 
buildings.” [1, p. 33A] 
Official 
A second key source of information on which this guidance is based are the Acceptable 
Solutions C/AS1-7, Paragraph 6. 
the 
The NZFS also recommends the use of the Fire Fighting Facilities Checklist (FFFC) to 
document NZFS agreement on specific sites access requirements.  The FFFC document can be 
found on the NZFS website (http://www.fire.org.nz/business-fire-safety/building-
design/Documents/Fire-Fighting-Facilities-Checklist.pdf)
under 
During the design of NZFS vehicle access, where appropriate the New Zealand Transport 
Agency (NZTA) guidelines should also be followed. 
Definitions 
The following definitions apply in this document: 
  Aerial appliance: A specialised emergency vehicle that has an aerial apparatus which 
Released 
elevates to height for suppression and/or rescue. 
  Allowable Bearing Pressure: The calculated pressure required to counter compression 
forces exerted by dead loads (i.e. the minimum strength required to maintain stability under 
a weight load). 
  Appliance: An emergency vehicle that provides firefighting, rescue or Hazardous Materials 
(HazMat) capability. 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 


 
  Carriageway: Any construction specifically designed to be traversed by vehicular traffic 
(may or may not include a sealed top surface layer). 
  Stabilisers: Fitted to aerial appliances to provide stability when the vehicle’s centre of 
gravity shifts during the operation of the aerial apparatus. 
  Hardstand area: An area designated and designed for use by a NZFS fire appliance and its 
crew, which can withstand the laden weight and associated loads of the vehicle in use. 
 
NZFS appliances 
Act
Types of NZFS fire appliances 
The NZFS fleet consists of different types of vehicles, which are designed to perform specific 
functions at an emergency incident.  Such vehicles are collectively known within fire service 
agencies as appliances. 
The vast majority of NZFS fire appliances comprise of a specially built body fitted on a multi 
axle heavy vehicle chassis.  Depending on the function of each vehicle, various levels of 
firefighting, rescue or hazardous material capabilities are provided by way of equipment 
Information 
carried. 
Some appliances perform specialised functions in the event of an emergency.  Besides the 
general appliances, the second main category of appliance is aerial appliances.  An aerial 
appliance has a specially built telescopic and/or articulated apparatus that elevates to height 
for fire suppression of large premises, or to rescue trapped occupants in multi-storey 
Official 
buildings.  Aerial appliances are larger and heavier than general appliances, and may be on 
either a two, three or even four axle heavy vehicle chassis. 
Note: The functions of an aerial appliance require that it is able to get relatively close to the 
the 
building or structure that it needs to attend. 
The NZFS categorises its appliances into six Types, where Types 1 to 3 represent the general 
appliances and Types 4 to 6 represent the aerial appliances
under 
While specifications vary between different appliances, the maximum parameters (i.e. worst 
case scenario) for NZFS appliances are shown in Table 1
 
 
Maximum parameters 
 
 
Gross vehicle mass 
25 t 
 
 
Maximum overall length 
12.6 m 
  Released 
 
Maximum overall width 
2.5 m (6 m when stabilisers are deployed) 
 
 
Required free height 
4 m 
 
Table 1: Maximum parameters for NZFS appliances 
 
 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 



 
Appliance type coverage 
All sites, buildings and structures across New Zealand (NZ) should ensure all NZFS appliances 
are given adequate access in the event of an emergency. 
When applicable, developers and planners must also ensure that adequate access is provided 
for aerial appliances.  The location of the site must be within the coverage area of an aerial 
appliance
 and the buildings or structures likely to require an aerial appliance during an 
emergency. 
To determine whether aerial appliance access is necessary for a given site, contact NZFS 
Operations through the local Fire Area office. 
Act
 
Access requirements 
Carriageway widths 
Carriageways should be wide enough to allow appliances to easily negotiate them, and 
provide sufficient room to allow vehicle crews to work with firefighting equipment around 
the vehicle. During an emergency, appliances will park along the carriageway in the most 
Information 
tactically advantageous position. 
Along straight carriageway sections, a minimum width of 4 m should be provided for general 
appliance access, and a minimum width of 6 m for aerial appliance access (see Figure 1). 
Note: Aerial appliances require additional width to fully extend their stabilisers. Where 
continuous 6 m clearance cannot be provided, NZFS may consider designated hardstand areas 
Official 
for aerial appliance operation. 
A clear passageway of no less than 3.5 m wide should be provided at site entrances, internal 
the 
entrances and between buildings. 
under 
Released 
 
Figure 1: Minimum carriageway widths along straight sections 
 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 



 
Along curved carriageway sections, a minimum inner radius of 6.3 m and outer radius of  
11.3 m should be provided for general appliance access, and a minimum inner radius of 5.2 m 
and outer radius of 12.5 m for aerial appliance access (see Figure 2). 
The distance between inner and outer turning arcs must allow for expected vehicle body 
swing.  The minimum distance between the inner and outer arcs should not be less than 5.0 m 
for general appliances and 7.3 m for aerial appliances (see Figure 2). 
Act
Information 
 
Figure 2: Minimum carriageway widths — curved sections 
Note: The radius dimensions specified above are for wall to wall clearance from body overhang, 
Official 
and do not represent the vehicle’s wheel tracks. 
Turning areas 
the 
Any carriageway not leading directly to an exit (i.e. dead end) should be provided with a 
turnaround area that prevents the need to perform multi-point turns. 
NZFS vehicles are required, and are designed, to perform a full 360° turn within a 25 m circle 
(wall to wall clearance) to meet NZTA requirements. 
under 
The minimum turning radius of turnaround areas should be no less than 11.3 m for general 
appliances, and 12.5 m for aerial appliances (see Figure 2). 
As per the NZTA guidelines, the Road Tracking Curves [2] as indicated in Table 2 should be 
considered. 
 
 
NZFS fire appliance type 
NZTA road tracking curve 
Released 
 
 
Type 1, 2, 3 
8 m Medium Rigid Truck 
 
 
Type 4, 5, 6 
Large Rigid Truck 
 
Table 2: NZFS fire appliance types in relation with the NZTA road tracking curves 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 




 
Ensuring clear access 
Site managers must ensure carriageways are not fully or partially obstructed in a manner that 
prevents unhindered access by appliances, at any time.  Moreover, it must be ensured that 
access routes are trafficable during all weather conditions. 
Note: Carriageways can be obstructed by parked vehicles, shipping containers, pallets, stored 
goods, industrial bins etc.
 
Perimeter security points (e.g. sliding/swinging gates, boom gates, bollards, vehicle security 
barriers) must not unnecessarily impede appliances from gaining access.  A minimum width of 
3.5 m and height of 4 m should be provided at site entrances, internal entrances and between 
Act
buildings. 
Kerb dimensions 
All kerbs constructed along the edges of a carriageway should be no higher than 250 mm, and 
should be free of vertical obstructions at least 300 mm back from the kerb face to allow 
clearance for front and rear body overhang. 
Information 
 
Official 
Figure 3: Carriageway kerb clearance dimensions 
Building and structure clearance height 
the 
An unobstructed clearance height of 4 m should be maintained above all access ways, 
including clearance from building construction, archways, gateways/doorways and 
overhanging structures (e.g. ducts, pipes, sprinklers, walkways, signs, beams, trees, hanging 
cables, etc.). 
under 
Released 
 
Figure 4: Building and structure clearance heights 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 




 
Note: Special consideration must be made where there are height restrictions in combination 
with gradient changes.  In some cases more than 4 m of clearance will need to be provided so the 

appliance can take the gradient change. 
Gradients (e.g. access ramps) 
NZFS prefers a ramp gradient of 1:8 or less.  The maximum negotiable ramp gradient is 1:5. 
Access ramps that follow a curved or circular profile in plan view should have a maximum 
gradient no greater than 1:10 (measured along the centre line). 
Note: The chassis of an appliance will twist and flex when negotiating the ramp, thus a lower 
Act
gradient is necessary. 
Ramps should not hinder vehicle response and should provide entry/exit clearances for 
appliances
Access ramps should have a smooth transition between the main ramp gradient and 
entry/exit gradients.  A minimum 4.0 m long 1:15 transition grade is preferred for both ramp 
approach and departure (see Figure 5). 
Information 
 
Official 
Figure 5: Maximum access ramp gradients 
When a change of gradient includes a recessed threshold, such as a gutter (e.g. for storm 
water drainage), consideration must be given to reduced approach and departure clearance 
the 
(see Figure 6). 
under 
Released 
 
Figure 6: Reduced gradient clearance due to gutter 
Note: As wheels recede into a gutter, the effective under-body clearance height at both front and 
rear overhanging sections are reduced due to the body slanting downwards.  This problem is 
exacerbated when the gutter depth is greater and/or when the overhang length is greater. 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 

link to page 9

 
Besides the general access gradients as indicated above, hardstand gradients are limited due 
to deployment of the stabilisers of aerial appliances.  Aerial appliances can only deploy their 
stabilisers and operate if the ground slope is within +/- 6°. 
Appliance weights (loads) 
Static loads of appliances 
Carriageways must maintain structural adequacy and integrity when under load from a fire 
appliance, with particular attention given to those supported, elevated or reinforced by  Act
structural members (e.g. suspended floors, ramps, wharfs, aprons etc.). 
The loads of appliances (exerted through wheels) used to determine forces acting through 
load-bearing structural members are provided in Figure 7.  Wheelbase distances between the 
front and back axles range from 3.7 to 5.5 m for general appliances, and 4.4 to 5.6 m for aerial 
appliances.  Distances between wheels - both longitudinal and lateral - may need 
consideration when calculating point loads for wheels. 
Note: Designers should be aware that the axle loads, as indicated in Figure 7, cannot be assumed 
to be evenly distributed over all wheels. 
Information 
Official 
the 
 
under Figure 7: Axle loads of appliances 
In general, access routes should be able to withstand a laden weight of up to 25 tonnes with 
an axle load of 8 tonnes, or have a load-bearing capacity of no less than the public roadway 
serving the property, whichever is the lower. 
Roadway pavements designed for aerial appliances shall withstand a vehicle of multiple axles 
spaced at no less than 2.5 m centres and each carrying 8.2 tonnes. 
The hardness of the carriageway surface must withstand the static pressure exerted by tyres 
Released 
of an appliance that is not greater than 850 kPa. 
Note: The NZFS recommends that pavements for fire appliance access are designed according to 
NZTA HN-HO-72 traffic loading specifications, in order to meet the load-bearing requirements. 
 
 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   
 
 



 
Dynamic loads (on aerial appliances
Aerial appliances are fitted with stabilisers that prevent the vehicle from overbalancing when 
the aerial apparatus is operating.  Aerial appliances will either have two stabilisers at the rear 
only, or two front and two rear stabilisers (see Figure 8). 
Act
 
Figure 8: General stabiliser arrangement on aerials 
Dynamic forces exerted through the stabilisers are caused by changing weight distribution 
and other forces, such as torsion moment forces, which are created by the extension and 
rotation of the aerial apparatus. 
Information 
Note: The ever-changing distribution of weight can cause up to 70% of the total vehicle weight 
to bear on a single stabiliser. 
The maximum dynamic loads and pressures exerted though a single stabiliser of the Bronto 
Skylift F44 RLX, having a fully loaded cage (500 kg) at maximum extension/outreach and 
under worst case rotation angle are: 
Official 
Maximum stabiliser force: 200 kN 
Maximum footplate pressure: 11 kg/cm²  (1079 kPa)  
the 
Maximum bearing plate (block) pressure: 2.8 kg/cm² (274 kPa) 
The maximum exerted pressure above should be considered when calculating the minimum 
Allowable Bearing Pressure (ABP) for the carriageway or hardstand area. 
under 
Dynamic forces exerted through the stabilisers are caused by changing weight distribution, 
and other forces such as torsion moment forces, which are created by the extension and 
rotation of the aerial apparatus. 
Vehicle hardstand requirements 
For a fire appliance to be effective it needs to be able to park in an area as close as possible to 
both the available water supply and the structure to be protected.  This area is termed the 
hardstand.  The exact location and extent of hardstands shall be determined in consultation 
Released 
with NZFS Operations. 
 
 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   10 
 
 




 
As indicated in the Building Code Clause C5.3, buildings must be provided with access for fire 
service appliances to a hardstand area from which there is an unobstructed path to the 
building within 20 m of: 
a)  firefighter access into the building and; 
b)  the inlets to automatic fire sprinkler systems or fire hydrant systems, where these are 
installed. 
If the floor area of a firecell is greater than 5000 m2, a hardstand area must be provided to 
more than one side of the respective firecell. 
Note: The above hardstand requirements do not apply to the following classified uses (as defined 
Act
in Clause A1 of the Building Code): Backcountry huts, detached dwellings, within household units 
in multi-unit dwellings, outbuildings, ancillary buildings
Designers should also refer to Paragraph 6 of the Applicable Acceptable Solution C/AS1-7 for 
the appropriate hardstand requirements.  Be aware that special care should be taken in case 
of Acceptable Solution Risk Groups SH (C/AS1) and SI (C/AS3).  A description of the different 
possible Risk Groups can be found in Table 1.1 of each of the Acceptable Solutions C/AS1-7.  
For example, in the case of a sleeping risk group as per C/AS1, the hardstand shall also be 
within 75 m of any point in any unit contained in the building, unless there is a sprinkler 
system installed that is compliant with NZS 4515. 
Information 
Specific guidance on the firefighting water supply near a hardstand can be found in the NZFS 
Firefighting Water Supplies Code of Practice SNZ PAS 4509:2008 [3].  Depending on the water 
supply circumstances, specific solutions and requirements can be found in this Code of 
Practice.  For example, if reticulated water supplies are unavailable or insufficient, alternative 
firefighting water sources might be required near the hardstand (see Figure 9).  In order to 
Official 
determine the exact water supply requirements (e.g. type water supply, type connection, etc.), 
contact NZFS Operations through the local Fire Area office. 
the 
Note: Fire districts may have a range of water supply systems such as a fully reticulated water 
supply system (in an urban water supply area), a rural water supply system that feeds a supply 
tank (in a rural water supply area), or a stand-alone tank supply using rain water or a local well 
or bore for maintaining its contents. 

under 
Released 
 
 
Figure 9: Examples of Suction (left) and Flooded (right) water supply sources near the hardstand 
 
 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   11 
 
 


 
References 
 
[1]  Ministry of Business Innovation and Employment, New Zealand Building Code Handbook, 2013.  
[2]  Land Transport New Zealand, New Zealand on-road tracking curves for heavy vehicles, 2007.  
[3]  New Zealand Fire Service Firefighting Water Supplies Code of Practice SNZ PAS 4509, Standards 
New Zealand, 2008.  
 
Act
Information 
Official 
the 
under 
Released 
New Zealand Fire Service 
   
 
Emergency vehicle access guidelines   12