F2 Fixed fire protection systems (NCI 25) 
 
F2 Fixed Fire Protection Systems (NCI 25) 
Purpose   
This document provides for: 
  safe and effective operations at calls to complexes protected by sprinkler, drencher, or 
other fixed fire protection systems. 
Contents 
Sprinkler Systems ................................................................................................................... 1 
Act
Gas Flooding Systems ............................................................................................................ 2 
Hazard Identification and Control: Fixed Fire Protection Systems ........................................... 3 
 
Chief Fire Officers’ responsibilities 
Chief Fire Officers will issue a local procedure on fixed fire protection systems when a risk 
identified during operational planning is significantly different to the general risks covered by this 
procedure.  
Information 
 
Sprinkler Systems   
Where a fire exists, and the sprinkler system allows, an appliance will be tasked to connect in 
and boost the sprinkler system.  
Official 
Systems that comply with NZ Standards will have a fire hydrant inlet located close to the valve 
house. 
the 
 
System Integrity   
On arrival, the OIC Fire will ensure that the integrity of the sprinkler system is in place by 
checking that: 
under 
  the main valve is open 
  floor isolation valves are open 
  the drain valve is closed 
  adequate water is flowing into the system (if not, boost pressure as described at the 
beginning of this section). 
Released 
 
Floor isolation valves 
Floor isolation valves are used: 
  to  isolate sections of the sprinkler system 
  to  reduce further damage once the fire has been extinguished 
  in preference to shutting down a whole system. 
NZFS Department of Operations and Training 
Page 1 of 3 
F2 Fixed fire protection systems December 2008 


















 
 
F2 Fixed fire protection systems (NCI 25) 
 
Building familiarisation will include the identification of floor isolation valves and their location 
(they have been mandatory in buildings with 6 or more floors since 1996). 
During a fire, where isolation valves are fitted, a firefighter will be stationed at the isolation valve 
on the fire floor. 
 
Salvage   
Early attention will be given to minimising water damage including early salvage by: 
  use of a sprinkler stopper tool 
Act
  use of a floor isolation valve (refer to „Floor isolation valves‟ above). 
  draining sprinkler heads and diverting water away.  
 
System Shutdown   
Sprinkler systems may be shut down at: 
  the main stop valve 
Information 
  floor isolation valve (preferable where applicable). 
The OIC Fire will instruct NZFS personnel to shut down all or part of the sprinkler system(s), 
only when: 
  appropriate extinguishing resources are in place  
  the fire is under control  
Official 
  more efficient use of the available water can be made where floor isolation valves are 
fitted 
the 
Whenever a sprinkler system is shut down, the owner/occupier of the building or their agent will 
be notified. 
 
Gas Flooding Systems   
under 
Operational planning will identify sites that are fitted with gas flooding systems.  
Local procedures will identify: 
  warning pre-activation 
  entry procedures 
  building layout/access 
Released 
  location and types of gas cylinders 
  the need to wear BA  
  covering deliveries or extinguishers  
  CO2 and nitrogen asphyxiates  
  valuables being protected 
  system operation and shutdown  
NZFS Department of Operations and Training 
Page 2 of 3 
F2 Fixed fire protection systems December 2008 











 
 
F2 Fixed fire protection systems (NCI 25) 
 
  ventilation  
  rescues. 
 
Smoke Cloak Security Systems  
There is an increasing use of “Smoke Cloak” security systems in some retail stores.  
NZFS personnel engaged in operational planning and/or building inspections will identify those 
premises that have smoke cloaks or similar security systems, and create local procedures to 
provide guidance on how to manage calls to premises with these installations. 
Act
This information will be relayed to responding crews. 
 
Hazard Identification and Control: Fixed Fire Protection Systems   
Hazard control 
All hazards will be controlled by eliminating, isolating where elimination is impracticable, or 
minimising, using one or more of the control methods listed in the following table: 
 
Information 
Hazards 
Control measures 
  all personnel will be trained in the risks to be 
Significant hazards:  
encountered and safe practices for working in 
environments where fixed fire protection systems 
  asphyxiation  
have operated  
Official 
  reduced visibility  
  operational planning and risk assessment  
  noise from fire alarm 
  briefing crew/s on plan of action and safety 
system 
measures  
 
the 
  structural firefighting uniform worn correctly  
  breathing apparatus & hearing protection 
  
 
under 
Released 
NZFS Department of Operations and Training 
Page 3 of 3 
F2 Fixed fire protection systems December 2008